Test Report

This type of power transformer has passed the test and its performance meets with the National Standards GB/T 1094.1 ~ 2-2013, GB/T 1094.3-2003, GB/T 1094.5-2008 and the technical parameters and GB/T 6451-2015 requirements. It has been checked up to the production standards and its final quality okeyed for sales, be qualified for delivery in conformity with Standards. 

Keywords:

Test Report

产品描述

  • 产品描述
    • Commodity name: Test Report

    This type of power transformer has passed the test and its performance meets with the National Standards GB/T 1094.1 ~ 2-2013, GB/T 1094.3-2003, GB/T 1094.5-2008 and the technical parameters and GB/T 6451-2015 requirements. It has been checked up to the production standards and its final quality okeyed for sales, be qualified for delivery in conformity with Standards. 

    Date of testing: 

    21st September, 2021

    Ambient Temp.:  

    26℃  

     NO.: 210

    82203

    1 Parameter

    Model

    S11-250 /11

    Serial Nos.

    2021

    82203

    Capacity

      250  kVA

    Rated Frequency

    50 Hz

    Rate V

    11000  /  700  -2425V

    Rated Current

    6.28/376.5A

    Insul. Class

    LI 95 AC 35/AC5

    Connection mode

    Dyn11

    Insul. Oil

    45# Transformer purposed oil

    Conditions

    Outdoor

    Phase

    3

    Cooling way

    ONAN

    Codes of P.

    1TY.710.150

    2 Earth V.

    Tapping stage

    High Voltage V

    Other Tapping V

    Lower V

    5

    11000

    13800±2×2.5 %

    230

    3 Insulation performance 

    Resistance

    Once to ground

    Secondary to ground

    Time of the secondary and ground

    МΩ

    2500

    11000±2×2.5 %

    700-2425

    4 Voltage ratio &connection group label verification

    High voltage winding HV

    Low winding LV

    Measurement deviation %

    Connection group

    Tapping stage

    Voltage kV

    Voltage kV

    AB/ab

    BC/bc

    CA/ca

    Verification

    11.55

    0.7-2.425

    0.23

    0.08

    0.02

    0.05

    Dyn11

    11.27

    0.08

    0.05

    0.04

    11

    0.06

    0.03

    0.02

    10.72

    0.06

    0.06

    0.01

    10.45

    0.07

    0.09

    0.07

    5 Wire-wound resistor

    Winding Group

    Position

    Real test values

    Max. Unbalance Rate %

    AB (Ω)

    BC (Ω)

    CA (Ω)

    High Voltage                            HV

    1

    12.94

    12.98

    12.96

    0.33

    2

    12.63

    12.67

    12.65

    3

    12.32

    12.36

    12.34

    4

    12.01

    12.05

    12.03

    5

    11.71

    11.74 

    11.72

    Low Voltage      LV

    Line resistance

    ab (mΩ)

    bc (mΩ)

    ca (mΩ)

    1.13

    6.094

    6.101

    6.163

    Phase resistance

    oa (mΩ)

    ob (mΩ)

    oc (mΩ)

    2.12

    3.047

    3.053

    3.112

    6  Applied voltage withstand test.

    Pressurized area

    Voltage Testing kV

    Test time S

    Conclusion

    High voltage to ground, low voltage

    35

    60

    PASS

    Low voltage to ground, high voltage

    5

    60

    7  Induced Overvoltage Withstand Test

    Applied voltage kV

    Induced voltage kV

    Induction

    Frequency

    Test time 

    Conclusion

        LV

    HV

    Multiple

    Hz

     S

    PASS

    0.46

    27.6

    2

    150

    40

    8  No load loss and no load current test

    Averaged voltage

    Effective voltage

    No-load Current  %

    No-load Loss kW

    kV

    kV

    0.7-2.425

    0.7-2.425

    0.66

    0.245

    9  Short circuit impedance and load loss measurement

    Winding Group

    Tapping place

    Applied Current A

    Short circuit impedance  %

    No-load Loss kW

    Total Loss kW

      HV-LV

    3

    6.28

    4.02

    1.915

    2.16

    10 Transformer oil test

    Density ≤ 0.895㎏/dm³                       

    Kinematical Viscosity 50°C≤11.6

    Flash Point ≥140°C

     Insulating Oil Dielectric Loss ≤0.005

    Acid Value ≤0.01mgKOH/g

    Ash  -  %

    Withstand voltage 45KV/2.5mm

    Oil number Domestic 45# type

    11 Sealing test

    The product can endure 20  Kpa pressure for 12 hours without leakage.

    Conclusion

      This type of power transformer has passed the test and its performance meets with the National Standards GB/T 1094.1 ~ 2-2013, GB/T 1094.3-2003, GB/T 1094.5-2008 and the technical parameters and GB/T 6451-2015 requirements. It has been checked up to the production standards and its final quality okeyed for sales, be qualified for delivery in conformity with Standards. 

    Tester:QC  4

    Evaluation Tester:QC  2

    Approved by:QA  1