Barbados Test Report

This type of power transformer has passed the test and its performance meets with the National Standards GB/T 1094.1 ~ 2-2013, GB/T 1094.3-2003, GB/T 1094.5-2008 and the technical parameters and GB/T 6451-2015 requirements. It has been checked up to the production standards and its final quality okeyed for sales, be qualified for delivery in conformity with Standards. 

Product Description

Date of testing: 

21st September, 2021

Ambient Temp.:  

26℃  

 NO.: 210

82203

1 Parameter

Model

S11-250 /11

Serial Nos.

2021

82203

Capacity

  250  kVA

Rated Frequency

50 Hz

Rate V

11000  /  700  -2425V

Rated Current

6.28/376.5A

Insul. Class

LI 95 AC 35/AC5

Connection mode

Dyn11

Insul. Oil

45# Transformer purposed oil

Conditions

Outdoor

Phase

3

Cooling way

ONAN

Codes of P.

1TY.710.150

2 Earth V.

Tapping stage

High Voltage V

Other Tapping V

Lower V

5

11000

13800±2×2.5 %

230

3 Insulation performance 

Resistance

Once to ground

Secondary to ground

Time of the secondary and ground

МΩ

2500

11000±2×2.5 %

700-2425

4 Voltage ratio &connection group label verification

High voltage winding HV

Low winding LV

Measurement deviation %

Connection group

Tapping stage

Voltage kV

Voltage kV

AB/ab

BC/bc

CA/ca

Verification

11.55

0.7-2.425

0.23

0.08

0.02

0.05

Dyn11

11.27

0.08

0.05

0.04

11

0.06

0.03

0.02

10.72

0.06

0.06

0.01

10.45

0.07

0.09

0.07

5 Wire-wound resistor

Winding Group

Position

Real test values

Max. Unbalance Rate %

AB (Ω)

BC (Ω)

CA (Ω)

High Voltage                            HV

1

12.94

12.98

12.96

0.33

2

12.63

12.67

12.65

3

12.32

12.36

12.34

4

12.01

12.05

12.03

5

11.71

11.74 

11.72

Low Voltage      LV

Line resistance

ab (mΩ)

bc (mΩ)

ca (mΩ)

1.13

6.094

6.101

6.163

Phase resistance

oa (mΩ)

ob (mΩ)

oc (mΩ)

2.12

3.047

3.053

3.112

6  Applied voltage withstand test.

Pressurized area

Voltage Testing kV

Test time S

Conclusion

High voltage to ground, low voltage

35

60

PASS

Low voltage to ground, high voltage

5

60

7  Induced Overvoltage Withstand Test

Applied voltage kV

Induced voltage kV

Induction

Frequency

Test time 

Conclusion

    LV

HV

Multiple

Hz

 S

PASS

0.46

27.6

2

150

40

8  No load loss and no load current test

Averaged voltage

Effective voltage

No-load Current  %

No-load Loss kW

kV

kV

0.7-2.425

0.7-2.425

0.66

0.245

9  Short circuit impedance and load loss measurement

Winding Group

Tapping place

Applied Current A

Short circuit impedance  %

No-load Loss kW

Total Loss kW

  HV-LV

3

6.28

4.02

1.915

2.16

10 Transformer oil test

Density ≤ 0.895㎏/dm³                       

Kinematical Viscosity 50°C≤11.6

Flash Point ≥140°C

 Insulating Oil Dielectric Loss ≤0.005

Acid Value ≤0.01mgKOH/g

Ash  -  %

Withstand voltage 45KV/2.5mm

Oil number Domestic 45# type

11 Sealing test

The product can endure 20  Kpa pressure for 12 hours without leakage.

Conclusion

  This type of power transformer has passed the test and its performance meets with the National Standards GB/T 1094.1 ~ 2-2013, GB/T 1094.3-2003, GB/T 1094.5-2008 and the technical parameters and GB/T 6451-2015 requirements. It has been checked up to the production standards and its final quality okeyed for sales, be qualified for delivery in conformity with Standards. 

Tester:QC  4

Evaluation Tester:QC  2

Approved by:QA  1